The threat of corrosion and contaminants in your electric power generator |
E/One Generator Gas Dryer |
Water, oil, and other contaminants cause corrosion in critical areas of electric power generators, resulting in diminished efficiency and increasing the likelihood of forced outages. Increased dew point levels also detract from generator efficiency by increasing windage losses. E/One's Generator Gas Dryer (GGD II) is a dual-chamber system that continuously dries and recirculates generator cooling gas — even when the generator is on turning gear, which is a critical time to maintain low dew point.
Column regeneration is automated and takes place based on programmable inlet and outlet dew point levels. The GGD II has a secondary, programmable, time-based regeneration feature, allowing you to set maximum times between regeneration (from 10 to 30 days).
Contact E/One to arrange a dew point site evaluation by our Field Service Technicians. We'll sample your hydrogen cooling gas with NIST-traceable portable dew point and hydrogen purity analyzers and then issue a report to site engineering regarding our findings.

| ELECTRICAL CHARACTERISTICS | |
| Input Voltage | 400/600 VAC Three Phase |
| Input Frequency | 50/60 Hz |
| Input Power | 3,000 Watts |
| Inrush Current | 3.5A |
| Ambient Temperature | 32 F to 125 F (0 C to 52 C) |
| Maximum Pressure | 100 psi |
| Ambient Location | Zone II, Group II, H2 |
| Output, Relays | 5A @ 250 VAC |
| 5A @ 30 VDC | |
| 100 mA @ 125 VDC | |
| Dew Point High, NO and NC | |
| Trouble, NO and NC | |
| Output, Signals | 4-20mA current output (self-powered) |
| Input Dew Point | |
| Outlet Dew Point | |
| 2-wire, Modbus RS232/485, 9600 Baud | |
| Inlet & Outlet Connections | 3/4" ANSI Class 150 RF Flanges |
| Vent Connection | 1/2" ANSI Class 150 RF Flange |
| Alternate Regeneration Connection | 1/4" Compression Fitting |
| Typical Flow Rate | 8-12 ACFM, Hydrogen |
| Typical H2 Consumption per Regeneration | 360 ft3 (10 meters3) |
|
Click here to download a PDF file |